Congratrulations! Haibian Power Equipment Co., Ltd. has 12kv & 24kv Gas insulated Switchgear successfully finished STL Membership ASTA test items.33kV ASTA test is under proceeding,welcome a world wide cooperators!

KYN28A-12 Armored Removable AC Metal Enclosed Switchgear

PRODUCT DESCRIPTION KYN28A-12(GZS1) type armored removable AC metal-enclosed switchgear (hereinafter referred to as "switchgear") is suitable for three-phase AC 50Hz power system for receiving and di

PRODUCT DESCRIPTION

KYN28A-12(GZS1) type armored removable AC metal-enclosed switchgear (hereinafter referred to as "switchgear") is suitable for three-phase AC 50Hz power system for receiving and distributing power and controlling, protecting and monitoring of the circuit in real time. The newly introduced and developed large current and high breaking switchgear can also be used as a high-voltage generator export.

The product is in line with GB3906 "3-35kV AC metal enclosed switchgear", GB/T11022 "common technical requirements of high-voltage switchgear and control equipment standard", IEC62271 "AC metal-enclosed switchgear and control equipment with rated voltage 1kV above 52kV and below".

Model and Meaning

KYN28A-12 Armored Removable AC Metal Enclosed Switchgear

The Main Technical Parameters

Item Unit Data
Rated power supply kV 3.6、7.2、12
Rate frequency Hz 50
Rated current of circuit breaker A 630、1250、1600、2000、2500、3150、4000
Rated current of switchgear A 630、1250、1600、2000、2500、3150、4000
Rated short-time withstand current(4s) kA 16、20、25、31.5、40、50
Rated peak withstand current (peak) kA 40、50、63、80、100、125
Rated short circuit breaking current kA 16、20、25、31.5、40、50
Rated short circuit closing current (peak) kA 40、50、63、80、100、125

Rated

Insulation

Level

1min power frequency Between the poles kV 24、32、42
withstand voltage Between fractures kV 24、32、48
Lightning impulse Between the poles kV 40、60、75
withstand voltage(peak) Between fractures kV 46、70、85
Protection class The enclosure is IP4X, compartment,and the circuit breaker compartment is IP2Xwhen the door is open.

Note: 1.The short-circuit capacity of the current transformer should be considered separately;
          2.See ZN63A-12 technical parameters in the corresponding sample.
          3.1000m-altitude rated current ≤ 1250A rated breaking current ≤ 31.5kA.
 

Structure diagram

KYN28A-12 Armored Removable AC Metal Enclosed Switchgear

Dimensions

KYN28A-12 Armored Removable AC Metal Enclosed Switchgear

Installation Dimension

KYN28A-12 Armored Removable AC Metal Enclosed Switchgear

Feedback